The customer is responsible to make sure that all necessary electrical work is done by a licensed electrical contractor in accordance to their local laws and/or regulations.
| Specification | Value |
|---|---|
| Voltage | 208-230 VAC, 1-phase (L1, L2/N) |
| Frequency | 50/60 Hz |
| Current | 20.0 Amp |
| Short-circuit current rating (SCCR) | 5 kA |
| Maximum system impedance for phase A | Z-phase A = 0.099 Ohm + j 0.062 Ohm |
| Maximum system impedance for neutral A | Z-neutral A = 0.066 Ohm + j 0.041 Ohm |
| Power Cord | 120 in. cable, bare wires (integrated) |
There is no plug for the M2+ (CE). The integrated power cable for the AON M2+ (CE) ends with bare wires.
A supply disconnecting device shall be provided for the M2+ (CE) machine, for example:
• a switch-disconnector, with or without fuses, in accordance with IEC 60947-3, utilization
category AC-23B or DC-23B.
• control and protective switching device suitable for isolation, in accordance with
IEC 60947-6-2.
• a circuit-breaker suitable for isolation in accordance with IEC 60947-2.
• any other switching device in accordance with an IEC product standard for that device and
which meets the isolation requirements and the appropriate utilization category and/or
specified endurance requirements defined in the product standard.
An overcurrent protection device must be provided for the M2+ (CE) machine, either a fused device or a circuit breaker. AON3D recommends sizing the overcurrent protection device to interrupt the circuit at 30A.
| Specification | Value |
|---|---|
| Voltage | 208-230 VAC, 1-phase (L1, L2/N) |
| Frequency | 50/60 Hz |
| Current | 24.5 Amp |
| Short-circuit current rating (SCCR) | 5 kA |
| Maximum system impedance for phase A | Z-phase A = 0.099 Ohm + j 0.062 Ohm |
| Maximum system impedance for neutral A | Z-neutral A = 0.066 Ohm + j 0.041 Ohm |
| Power Cord | 82 in. Power Cord , 30 A, L6-30P (integrated) |
Do not use power cord(s) other than the unit(s) supplied with the AON3D machine. Always use a grounded three-prong power outlet for AON M2+ (R-NZ), AON M2+, AON-M2 2020 and AON-M2 machines.
| Specification | Value |
|---|---|
| Machine Circuit | |
| Voltage | 200-240 VAC, 1-phase (L1, L2/N) |
| Frequency | 50/60 Hz |
| Current | 18 Amp |
| Power Cord | 120 in. Power Cord, 20 A, 12 AWG, IEC-320-C19 to NEMA L6-20P |
| Vacuum Circuit | |
| Voltage | 120 VAC |
| Frequency | 50/60 Hz |
| Current | 5 Amp |
| Power Cord | 120 in. Power Cord, 10 A, 18 AWG, IEC-320-C13 to NEMA 5-15P |
Do not use power cord(s) other than the unit(s) supplied with the AON3D machine. Always use a grounded three-prong power outlet for AON M2+ (R-NZ), AON M2+, AON-M2 2020 and AON-M2 machines.
| Specification | Value |
|---|---|
| Voltage | 208-230 VAC, 1-phase (L1, L2/N) |
| Frequency | 50/60 Hz |
| Current | 16 Amp |
| Power Cord | 120 in. Power Cord, 20 A, 12 AWG, IEC-320-C19 to NEMA L6-20P |
Do not use power cord(s) other than the unit(s) supplied with the AON3D machine. Always use a grounded three-prong power outlet for AON M2+ (R-NZ), AON M2+, AON-M2 2020 and AON-M2 machines.